Size FWU, CDU, and Chiller counts from IT load, with configurable N / N+1 / N+2 / N+3 / 2N / 2N+1 redundancy — then export a formatted Excel report.
Each count is the minimum number running (N) plus the redundancy you pick per equipment.
FWU is additionally rounded up to the next even number when the total is odd, since FWUs are installed in matched pairs — CDU and Chillers aren't paired that way, so they aren't rounded.
The Cooling Equipment Calculator sizes how many Fan Wall Units (FWU), Coolant Distribution Units (CDU), and Chillers a data hall needs to reject its IT heat load, given how that load splits between air and liquid cooling and whatever redundancy scheme your design standard requires — then exports the full calculation as a formatted Excel report you can attach to a design package.
Modern racks rarely cool purely one way. Air Ratio is the share of your total IT load rejected by traditional air cooling — CRAH/FWU units moving conditioned air across the room — while Liquid Ratio is the share handled by direct liquid cooling (cold plates or immersion) via CDUs, which transfer heat straight from the chip or chassis into a liquid loop without ever touching room air. A rack with a mix of standard 1U/2U servers and dense GPU trays, for example, might realistically split 50/50; a fully liquid-cooled AI cluster might run 80–95% liquid. These two ratios should sum to 100% of your total IT load.
Every equipment count here starts from N — the bare minimum number of units actually needed to reject the calculated load, with zero spares. From there:
Which scheme to use is a design/Tier decision (driven by ANSI/TIA-942 or Uptime Institute Tier requirements, or your own internal standard) — this tool doesn't prescribe one, it just applies whichever you pick consistently across FWU, CDU, and Chiller.
For FWU and CDU, the tool first works out how much of the IT load (in kW) each system actually has to reject — IT Load × its ratio (Air or Liquid), grossed up by that equipment's own safety factor — then divides by the single unit's rated capacity and rounds up to a whole number of units, before applying the redundancy multiplier/addition above:
The Safety Factor on each equipment type is your own design margin — headroom above the calculated load to cover future growth, measurement uncertainty, or manufacturer derating — and is applied before rounding, not after.
Check for the even-number rounding: FWUs are installed in matched pairs, so an odd result is always bumped up by one to make a pair — the calculator shows this adjustment directly under the result whenever it applies.
They should, since together they represent your whole IT load — but the calculator doesn't enforce this, so you can experiment with partial or hypothetical splits if you're exploring options.
That depends on your facility's target Tier/reliability level and your own engineering standard — this tool doesn't recommend one, it just applies whichever N/N+1/N+2/N+3/2N/2N+1 scheme you select consistently to every equipment count.
Yes, completely free, with no account and no server-side storage — every calculation and the Excel export are generated locally in your browser.